Mostrar el registro sencillo del ítem

Thermal response and failure mode evaluation of a dry-type transformer

dc.contributor.authorBlanco Alonso, Pelayo Enol
dc.contributor.authorMeana Fernández, Andrés 
dc.contributor.authorFernández Oro, Jesús Manuel 
dc.date.accessioned2017-10-31T10:48:33Z
dc.date.available2017-10-31T10:48:33Z
dc.date.issued2017
dc.identifier.citationApplied Thermal Engineering, 120, p. 763-771 (2017); doi:10.1016/j.applthermaleng.2017.04.007
dc.identifier.issn1359-4311
dc.identifier.urihttp://hdl.handle.net/10651/44235
dc.description.abstractIn this work, the safe working limits of a 10 kVA dry-type transformer with H-class insulation are determined by modeling its thermal response in different scenarios using numerical simulations (CFD). A numerical model of the heat transfer from the transformer to its surroundings by natural convection has been developed. Firstly, a steady regime with the transformer working at full load at an ambient temperature of 300 K is studied in order to gain insight into the heat transmission mechanisms. Then, a series of 32 steady simulations with different load and ambient conditions is performed to characterize insulation aging due to overheating. Finally, a second group of 9 transient simulations is employed to assess the transformer failure time under an overload situation. The results show a coupling between the thermal and flow fields. The hot spot temperatures obtained by the model are consistent with previous experimental observations and the time that the transformer resists an overload has been calculated. The results obtained allow the prediction of the thermal behavior of a transformer under different scenarios, reducing the need for instrumentation, as well as experimental tests which result in the loss of the testing transformer.
dc.description.sponsorshipThis work has been supported by the ‘‘FPU” predoctoral research scholarship provided by the Spanish Ministry of Education, Culture and Sports.
dc.format.extentp. 763-771
dc.language.isoeng
dc.relation.ispartofApplied Thermal Engineering
dc.rights© 2017 Elsevier Ltd
dc.rightsCC Reconocimiento – No Comercial – Sin Obra Derivada 4.0 Internacional
dc.rights.urihttp://creativecommons.org/licenses/by-nc-nd/4.0/
dc.sourceScopus
dc.source.urihttps://www.scopus.com/inward/record.uri?eid=2-s2.0-85018490413&doi=10.1016%2fj.applthermaleng.2017.04.007&partnerID=40&md5=d66ff850586b7d1a247bc949635717c3
dc.titleThermal response and failure mode evaluation of a dry-type transformer
dc.typejournal article
dc.identifier.doi10.1016/j.applthermaleng.2017.04.007
dc.relation.projectIDMECD
dc.relation.publisherversionhttp://dx.doi.org/10.1016/j.applthermaleng.2017.04.007
dc.rights.accessRightsopen access


Ficheros en el ítem

untranslated

Este ítem aparece en la(s) siguiente(s) colección(ones)

Mostrar el registro sencillo del ítem

© 2017 Elsevier Ltd
Este ítem está sujeto a una licencia Creative Commons