Show simple item record

Strategies for the connection of distributed power generation units to distorted networks

dc.contributor.authorBlanco Charro, Cristian 
dc.contributor.authorDíaz Reigosa, David 
dc.contributor.authorBriz del Blanco, Fernando 
dc.contributor.authorGuerrero Muñoz, Juan Manuel 
dc.date.accessioned2015-06-23T10:19:38Z
dc.date.available2015-06-23T10:19:38Z
dc.date.issued2014
dc.identifier.isbn978-1-4799-5776-7
dc.identifier.urihttp://hdl.handle.net/10651/31411
dc.description.abstractConnection of Distributed Power Generators (DPGs) to a utility grid requires the synchronization between the DPG and the grid voltages with the goal of controlling the power flow and limiting the currents at instant that the switch or breaker closes. Synchronization methods typically match the positive sequence voltage component of the two systems being connected, the connection being realized when the error is smaller than a pre-set threshold. While synchronization using the positive sequence voltage provides adequate results in the case of undistorted grid voltages, it can be inadequate if the grid is polluted, e.g. in case of weak grids. Instantaneous voltage mismatches between the DPG and the grid, e.g. due to the harmonic content or unbalances in the grid and/or DPG voltages..., at the instant that the breaker closes, can cause overcurrents and result in unwanted protection tripping or equipment damage, even if the corresponding positive sequence voltages perfectly match. This paper analyzes the synchronization and connection of DPGs to highly distorted grids with the goal of limiting the overcurrent due to voltage mismatch. Once the connection is realized, a transition to the conventional positive sequence voltage based synchronization occurs, as this is adequate to control the power flow in steady state
dc.description.sponsorshipThis work was supported in part by the Research, Technological Development and Innovation Programs of the Ministry of Science and Innovation under grant MICINN-10-CSD2009-00046 and by the Personnel Research Training Program funded by the Regional Ministry of Education and Science of the Principality of Asturias under grant BP11-107
dc.format.extentp. 3378-3385spa
dc.language.isoengspa
dc.publisherIEEEspa
dc.relation.ispartof2014 IEEE Energy Conversion Congress and Exposition (ECCE)spa
dc.rights© IEEE
dc.titleStrategies for the connection of distributed power generation units to distorted networksspa
dc.typebook partspa
dc.identifier.doi10.1109/ECCE.2014.6953859
dc.relation.projectIDMEC/MICINN-10-CSD2009-00046
dc.relation.projectIDFICYT/BP11-107
dc.relation.publisherversionhttp://dx.doi.org/10.1109/ECCE.2014.6953859spa
dc.rights.accessRightsopen access
dc.type.hasVersionAM


Files in this item

untranslated

This item appears in the following Collection(s)

Show simple item record