Elimination of the transfer time effects in line-interactive and passive standby UPSs by means of a small-size inverter
Subject:
Terms—Line-Interactive UPSs
Hysteretic controller
Transfer time in UPSs
Publication date:
Editorial:
IEEE
Publisher version:
Citación:
Descripción física:
Abstract:
The main drawback of line-interactive and passive standby uninterruptible power supplies (UPS) is the transfer time when changing from normal mode of operation to battery mode of operation. During this time, the critical loads protected by the UPS are under the influence of the grid disturbance that forced the mode change. On the other hand, equipment protected by a double-conversion UPS is never affected by disturbance in the mains. Unfortunately, the efficiency of this topology is lower and its size and cost are considerably higher. Hence, the elimination of the transfer process between modes in line-interactive and passive standby UPSs would make them more competitive than double-conversion UPSs in many situations. In this paper, a method for eliminating the transfer time is proposed. It is based on a half-bridge inverter with a hysteretic controller whose output voltage is only applied to the load during the transfer time. Considering the random nature of the grid failures and the short duration of the transfer time, the design and selection of the components are nothing but standard. This also leads to a nonstandard hysteretic controller that needs to be fully analyzed. Experimental results are provided for a 750-W line-interactive UPS whose transfer time of 4 ms was eliminated by the proposed system
The main drawback of line-interactive and passive standby uninterruptible power supplies (UPS) is the transfer time when changing from normal mode of operation to battery mode of operation. During this time, the critical loads protected by the UPS are under the influence of the grid disturbance that forced the mode change. On the other hand, equipment protected by a double-conversion UPS is never affected by disturbance in the mains. Unfortunately, the efficiency of this topology is lower and its size and cost are considerably higher. Hence, the elimination of the transfer process between modes in line-interactive and passive standby UPSs would make them more competitive than double-conversion UPSs in many situations. In this paper, a method for eliminating the transfer time is proposed. It is based on a half-bridge inverter with a hysteretic controller whose output voltage is only applied to the load during the transfer time. Considering the random nature of the grid failures and the short duration of the transfer time, the design and selection of the components are nothing but standard. This also leads to a nonstandard hysteretic controller that needs to be fully analyzed. Experimental results are provided for a 750-W line-interactive UPS whose transfer time of 4 ms was eliminated by the proposed system
ISSN:
Patrocinado por:
This work has been supported by projects MICINN-10-CSD2009-00046 and MICINN10-DPI2010- 21110-C02-0